Weather Masters, Inc.  provides plumbing, heating  & Air Conditioning repair and installation services in Chandler, AZ and surrounding areas.

Check out what some of our customers are saying about Weather Masters, Inc.

Local Reviews
for Chandler, AZ

Weather Masters, Inc. Rated 5.0 out of 5 stars based on 10 customer reviews

Map of Chandler, AZ

On time and great service




Review of Weather Masters, Inc.


Map of Chandler, AZ

Chris was great!




Review of Weather Masters, Inc.


Map of Chandler, AZ

Thank you!




Review of Weather Masters, Inc.

Jason did a very good job. We got a thorough inspection at a fair price. He gave us a full report when he was finished. Appreciate the good service!


Map of Chandler, AZ

Jason was courteous efficient and knowledgeable




Review of Weather Masters, Inc.


Map of Chandler, AZ

Service was great




Review of Weather Masters, Inc.

Very thorough


Map of Chandler, AZ

We had Jason as our service man and thought he was great and very polite




Review of Weather Masters, Inc.


Map of Chandler, AZ

good




Review of Weather Masters, Inc.

good job


Map of Chandler, AZ

Great Service




Review of Weather Masters, Inc.


Map of Chandler, AZ

Great Service




Review of Weather Masters, Inc.

Very professional and efficient.


Map of Chandler, AZ

Great Service




Review of Weather Masters, Inc.

Very pleasant and professional service.


Keith H.

Keith H.

replaceing condenser fan motor on a rooftop package heat pump commercial

Near W Chandler Blvd, Chandler, AZ 85226
Chris R.

Chris R.

PROBLEM 37 PT INSPECTION TRANE DIAGNOSIS ALL MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME UNIT IS COOLING WITH A 20 PLUS DEGREE TEMPERATURE SPLIT ACROSS THE COIL 10 MFD RUN CAPACITOR IS WEAK THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTOR /RECOMMEND REPLACING THE CAP REPLACED 10 MFD RUN CAPACITOR UNDER WARRANTY TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COIL FLUSHED DRAIN

Near W Gila Ln, Chandler, AZ 85224
Stuart M.

Stuart M.

PERFORMED PMP INSPECTION ON TWO SPLIT GAS AC UNITS CHECKED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURERS RANGE VERIFIED TEMP SPLIT ACROSS COILS CLEANED OUTDOOR COILS TIGHTENED ELECTRICAL CONNECTIONS CHECKED IN RUSH AMPS OF COMPRESSORS INSPECTED CONDITION OF UNITS UNITS RUNNING IN COOLING AT TIME OF INSPECTION. DOWNSTAIRS UNIT HAS WEAK 5 MF RUN CAPACITOR. CAPACITOR WAS REPLACED AT TIME OF INSPECTION. WHILE RUNNING MOTOR WITH WEAK CAPACITOR MAY HAVE CAUSED PERMANENT INTERNAL DAMAGE. WEATHER MASTERS RECOMMENDS FOLLOW UP INSPECTION IN FALL FOR HEATING SIDE OF SYSTEM.

Near S Nash Way, Chandler, AZ 85286
Stuart M.

Stuart M.

PROBLEM: UNIT NOT COOLING DIAGNOSIS: OFM MOTOR SUFFERED PERMANENT INTERNAL DAMAGE PREVIOUSLY DUE TO FAILED CAPACITOR. OFM NOT FUNCTIONING AT TIME OF INSPECTION AND DUE TO AGE NEW UNIT RECOMMENDED TO BE INSTALLED. SENT CUSTOMER ESTIMATE FOR NEW UNIT WAITING APPROVAL.

Near S Pinnacle Dr, Chandler, AZ 85286
Chris R.

Chris R.

PROBLEM NO COOL A/H CARRIER FA4BNFC60000AAAA 3604A73739 R-22 CONDENSER PAYNE PH13NR06000GAKAA 1314X74415 DIAGNOSIS FAILED BLOWER MOTOR /BLOWER WHEEL IS DAMAGED COIL IS VERY RUSTED/FOUND A LEAK AT THE EQUILIZER TUB CONNECTION ON THE SUCTION LINE DUE TO THE OVERALL CONDITION OF THE UNIT WE RECOMMEND REPLACING THE UNIT DRAIN PAN IS FULL OF DEBRIS AND RUST COMPRESSOR MAY HAVE TAKEN INTERNAL DAMAGE SYSTEM IS R-22

Near S Mosley Dr, Chandler, AZ 85249
Keith H.

Keith H.

Weak 35\5 dual capacitor. TESTED both units in cooling. TESTED FREON LEVELS amp draws and run capcitors. Repair. Replaced 35/5 dual run cap under warranty

Near S Tumbleweed Ct, Chandler, AZ 85248
Chris R.

Chris R.

PROBLEM 37 PT INSPECTION @2 NO COOL ON DOWNSTAIRS UNIT UPSTAIRS /DAY AND NIGHT PHR53000KTP0A1 C172932806 40/5 DUAL RUN CAPACITOR IS SHOWING WEAR BUT STILL WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME /MAY NEED TO BE REPLACED AT NEXT VISIT ALL MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME UNIT IS COOLING WITH A 20 DEGREE SPLIT ACROSS THE COIL NO OTHER ISSUES AT THIS TIME DISCOUNT 69.99 IF CUSTOMER BUYS A NEW UNIT

Near E Ironwood Dr, Chandler, AZ 85225
Chris R.

Chris R.

TRANE TTR060C100A2 L434SWDBF DIAGNOSIS UNIT IS SHOWING HEAVY WEAR DUE TO AGE AND USAGE RUSTED EVAPORATOR COIL COIL POSSIBLE DIRTY / WE WOULD NEED FURTHER DIAGNOSTICS TO PROPERLY DETERMINE RUSTED SECONDARY DRAIN PAN WEAK 5MFD AND 10 MFD RUN CAPACITORS /THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTORS CHARGE LOOKS LOW AT THIS TIME /WE WOULD NEED TO VERIFY CONDITION OF THE EVAPORATOR COIL TO PROPERLY CHARGE THE UNIT WE DUE NOT RECOMMENDED ANY COSTLY REPAIRS ON THIS UNIT CUSTOMER DECLINED ANY REPAIRS AT THIS TIME

Near W Nolan Way, Chandler, AZ 85248
Keith H.

Keith H.

PROBLEM: NO COOL/ NO INDOOR FAN RUNNING. DIAGNOSIS: UPON ARRIVAL THE SYSTEM WAS TURNED OFF. I TURNED THE SYSTEM ON AND FOUND UNIT TO FUCTION CORRECTLY. INDOOR AND OUTDOOR FANS TURN ON. COMPRESSOR TURNED ON AND THE SYSTEM BEGAN TO COOL. PERFORMED A MAINTENANCE ON THE ROOF TOP PACKAGE UNIT. OVERALL CONDITION IS SYSTEM SHOWNING NORMAL WEAR DUE TO AGE. TIGHTEN ELECTRICAL CONNECTIONS. HOSED OFF THE OUTDOOR COIL. TESTED FREON LEVELS. TESTED MOTOR AMP DRAWS AND CAPACITORS. CONDENSER FAN MOTOR SHOWING WEAR. LEAKING BEARINGS. MOTOR MAY HAVE ISSUES WHEN THE SUMMER TEMPS RISE. NOTE: IF THE INDOOR FAN FAILS TO RUN AGAIN. WEATHER MASTERS RECOMMENDS LEAVING SYSTEM RUNNING CALL IMMEDIATLY SO WE CAN SEE THE ISSUE AS IT A OCCURES. MODEL 4WCZ6036A1000AA SERAL 8084WLJ9H

Near N Comanche Dr, Chandler, AZ 85224
Chris R.

Chris R.

REPLACE 1/8HP BLOWER MOTOR AND WHEEL WE WILL NEED TO ORDER PARTS/5 TO 7 BUSINESS DAY FOR ARRIVAL 5/2/19 MADE RECOMMENDED REPAIRS /UNIT IS COOLING AT THIS TIME

Near W Chandler Blvd, Chandler, AZ 85225
Keith H.

Keith H.

PROVIDE ESTIMATE FOR WIRELESS SENSORS.

Near W Chandler Blvd, Chandler, AZ 85225
Stuart M.

Stuart M.

Weather Masters successfully completed a 37 point inspection - weather Masters tightened all electrical fittings - checked all Freon levels and pressures - checked amperage of indoor and outdoor motor. Working at intended anprage -Ensured run capacitor is running with proper MFD's and is not leaking - subcool is 10 -examined indoor and outdoor coil. Outdoor coil was cleaned with water -temperature split is normal at 18 -thermostat is working as should -filter is changed regularly and is currently clean -customer says unit is working well At this time, the system is running normally.

Near N Sunset Dr, Chandler, AZ 85225
Stuart M.

Stuart M.

PROBLEM: INDOOR FAN NOT TURNING ON. DIAGNOSIS: BLOWER MOTORS BEARINGS HAVE GONE OUT SND BLOWER WHEEL IS NOW BENT RECOMMEND REPAIRS: REPLACE BLOWER MOTOR AND WHEEL WITH OEM PARTS. INCLUDES CAPACITOR

Near E Scorpio Pl, Chandler, AZ 85249
Chris R.

Chris R.

PROBLEM WO/16784 37PT INSPECTION @2 UPSTAIRS /DAY AND NIGHT N4A530GKC101 E161100098 DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN THE COOLING MODE AND THE UNIT IS COOLING WITH A 20 DEGREE SPLIT ACROSS THE EVAPORATOR /THIS IS WITHIN MANUFACTURE SPECIFICATIONS THE 40/5 DUAL RUN CAPACITOR IS SHOWING WEAR BUT STILL WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME /MAY NEED TO BE REPLACED AT NEXT VISIT CONDENSER FAN MOTOR IS LEAKING OIL AND MAY FAIL PREMATURELY BECAUSE OF THE HIGH AMBIENT TEMPERATURES ALL MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME NO RECOMMENDED REPAIRS AT THIS TIME TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COIL FLUSHED DRAIN DOWNSTAIRS CA5536VKD1 L961676501 DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN THE COOLING MODE AND THE UNIT IS COOLING AT WITH A 20 DEGREE SPLIT ACROSS THE EVAPORATOR COIL DIRTY BLOWER WHEEL AND MOTOR /POSSIBLE DIRTY EVAPORATOR COIL /DO TO AGE AND CONDITION COSTLY REPAIRS ARE NOT RECOMMENDED THE 7.5 MFD RUN CAP

Near W Peninsula Cir, Chandler, AZ 85248
Robert T.

Robert T.

REPLACE EVAPORATOR COIL UNDER WARRANTY 15LBS 410 REFRIGERANT /NO WARRANTY REFRIGERANT REPLACE CONDENSER FAN MOTOR AND DUAL RUN CAPACITOR UNDER WARRANTY REPLACE VARIABLE SPEED BLOWER MOTOR UNDER WARRANTY

Near N Bradley Dr, Chandler, AZ 85226
Chris R.

Chris R.

FILTER MAINTENANCE NO COOL UNIT #4/WATER RM ICP RHS048H0XAOAAAA-- C121770048 DIAGNOSIS INDOOR BLOWER WHEEL AND MOTOR HAVE FAILED DUE TO A RUSTED BLOWER WHEEL AND RUSTED BLOWER HOUSING THIS WILL CAUSE THE REFRIGERANT TO LIQUEFY AND WASH THE OIL OUT OF THE COMPRESSOR /THE COMPRESSOR MAY HAVE TAKEN INTERNAL DAMAGE RECOMMEND REPLACING BLOWER ASSEMBLY /BLOWER MOTOR AND WHEEL /WE EVALUATE THE SYSTEM AFTER THE REPAIRS HAVE BEEN MADE BLOWER housing will take 60 days to come in

Near W Chandler Blvd, Chandler, AZ 85225
Chris R.

Chris R.

PROBLEM PMP VISIT /UNIT MAKING LOUD NOISE/RUNNING CONTINUOUSLY DAY AND NIGHT C4A648GKD200 E093416390 COIL/ASPEN ACE48D44227R064 H09-00010297 C8MPV100J20C1 A092644856 DIAGNOSIS UNIT IS VERY LOW ON REFRIGERANT /THIS WILL CAUSE INTERNAL DAMAGE TO THE COMPRESSOR CONDENSER IS LEAKING HEAVY OIL/MAY FAIL PREMATURELY BLOWER WHEEL IS DIRTY /THIS MAY HAVE CAUSED INTERNAL DAMAGE TO THE MOTOR BLOWER MOTOR HAS A INTERMITTENT NOISE /MAY BE INTERNALLY DAMAGED FROM RUNNING WITH A DIRTY BLOWER WHEEL WE WILL MAKE REPAIRS UNDER WARRANTY

Near N Bradley Dr, Chandler, AZ 85226
Chris R.

Chris R.

PROBLEM T-STAT NOT WORKING PROPER DIAGNOSIS BATTERIES ARE WEAK /T-STAT IS OLD AND OUT OF CALIBRATION

Near E Butler St, Chandler, AZ 85225
Chris R.

Chris R.

PROBLEM WO 16817 T- STAT NOT WORKING DIAGNOSIS BATTERIES NEED TO BE REPLACED REPLACED BATTERIES /UNIT CYCLED ON RECOMMEND FULL MAINTENANCE ON SYSTEM

Near W Ray Rd, Chandler, AZ 85224
Chris R.

Chris R.

PROBLEM SRP INSPECTION DAY AND NIGHT C4A460GKD200 E091302838 VERIFIED SEQUENCE OF OPERATION IN THE COOLING MODE AND THE UNIT IS COOLING WITH 9 DEGREES OF SUBCOOLING/ THIS IS THE RECOMMEND TEMPERATURE FOR THE UNIT 70/5 DUAL RUN CAPACITOR IS SHOWING WEAR BUT STILL WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME /MAY NEED TO BE REPLACE AT OR BEFORE NEXT INSPECTION TEMPERATURE SPLIT ACROSS THE EVAPORATOR COIL IS WITHIN SPEC THE FURNACE HAS VERY LIMITED ACCESS /I COULD NOT FLUSH THE DRAIN/WE RECOMMEND INSTALLING A SAFTEY DRAIN SWITCH TO PROTECT THE HOME FROM WATER DAMAGE IN THE EVENT THE DRAIN SHOULD BACK UP/ALONG WITH THAT RECOMMENDATION ATTACHED ARE MORE ADD ON TO HELP WITH THE PROTECTION AND OPERATION OF THE SYSTEM TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COIL NO CHARGE /RETURN TO CHECK A/C

Near S Sean Ct, Chandler, AZ 85286
Stuart M.

Stuart M.

PERFORMED PMP INSPECTION ON ONE SPLIT GAS AC UNIT CHECKED AMP DRAW OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURERS RATING VERIFIED TEMP SPLIT ACROSS COIL TIGHTENED ELECTRICAL CONNECTIONS INSPECTED CONDITION OF UNIT UNIT RUNNING NORMALLY IN COOLING AT TIME OF INSPECTION. UNIT HAS HAD OUTDOOR UNIT REPLACED AND LEFT ORIGINAL FURNACE IN ATTIC. START ASSIST CAPACITOR INSTALLED AT TIME OF INSPECTION. WEATHER MASTERS RECOMMENDS FOLLOW UP INSPECTION IN FALL FOR HEATING SIDE OF SYSTEM.

Near E San Tan St, Chandler, AZ 85225
Chris R.

Chris R.

PROBLEM 1ST PMP VISIT 2 UNITS /3 VISITS LEFT DAY AND NIGHT KITCHEN N4H430GKG101 E160913421 MASTER N4H436GKG201 E160506413 DIAGNOSIS 45/5 AND THE 35/5 DUAL RUN CAPACITORS HAVE FAILED FOR BOTH UNITS/ THIS WILL ALLOW INTERNAL DAMAGE TO CONDENSER FAN MOTORS AND COMPRESSOR AIR SRUBBERS NEED LAMPS REPLACED @2 VERIFIED SEQUENCE OF OPERATION IN THE COOLING MODE FOR BOTH UNIT/BOTH UNITS ARE COOLING AT THIS TIME REPAIRS REPLACED 45/5 AND 35/5 DUAL RUN CAPACITORS UNDER WARRANTY TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COILS FLUSHED DRAINS

Near W Ironwood Dr, Chandler, AZ 85226
Chris R.

Chris R.

37PT INSPECTION CUSTOMER WILL RESCHEDULE AFTER INSPECTOR COMES

Near N Danyell Dr, Chandler, AZ 85225
Keith H.

Keith H.

PERFORM 37PT INSPECTION ON 2 SYSTEMS. DIAGNOSIS: BOTH SYSTEMS ARE RUNNING FINE WITH NO ISSUES AT THIS TIME. - TESTED FREON LEVELS - TESTED MOTOR AMPS ON COMPRESSOR, INDOOR FAN AND OUTDOOR FAN. - TIGHTEN ELECTRICAL CONNECTIONS. - HOSED OFF THE OUTDOOR COIL. - FLUSHED THE CONDENSATE LINES. - INSPECTED DUCT CONNECTIONS. - VERIFIED SEQUENCE OF OPPERATION. BOTH UNITS ARE RUNNING NORMAL WITH NO ISSUES. RECOMMEND A FOLLOW UP VISIT IN THE FALL TO SERVICE THE FURNACE. WEATHER MASTERS RECOMMEND SIGNING UP FOR OUR PREVENTITIVE MAINENANCE PROGRAM. COVERS 4 INSPECTIONS TWO PER YR

Near E Scorpio Pl, Chandler, AZ 85249
Stuart M.

Stuart M.

PERFORMED 37 POINT INSPECTION ON TWO SPLIT GAS AC UNITS CHECKED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURERS RATING VERIFIED TEMP SPLITS ACROSS COILS TIGHTENED ELECTRICAL CONNECTIONS CLEANED OUTDOOR COILS INSPECTED CONDITION OF UNITS UNITS RUNNING IN COOLING AT TIME OF INSPECTION. BOTH OUTDOOR FAN MOTORS ARE DRAWING EXCESSIVE AMPS CAUSING PERMANENT INTERNAL DAMAGE. WEATHER MASTERS RECOMMENDS REPLACEMENT OF MOTORS.

Near E Tonto Pl, Chandler, AZ 85249
Stuart M.

Stuart M.

PROBLEM: LOUD NOISE COMING FROM CEILING DIAGNOSIS: ISSUE MOST LIKELY CAUSED BY PLUMBING ISSUE. ALL UNITS RAN NORMALLY AT TIME OF SERVICE CALL WITH NO UNUSUAL SOUND BEING EMITTED. ROOMS WHERE SOUND WAS HEARD HAVE EXTRA WATER LINES GOING TO THEM.

Near W Chandler Blvd, Chandler, AZ 85225
Stuart M.

Stuart M.

PERFORMED 37 POINT INSPECTION ON TWO SPLIT GAS AC UNITS CHECKED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURERS RATING VERIFIED TEMP SPLIT ACROSS COILS TIGHTENED ELECTRICAL CONNECTIONS INSPECTED CONDITION OF UNITS BOTH UNITS RUNNING IN COOLING AT TIME OF INSPECTION HOWEVER DOWNSTAIRS UNIT HAS OUTDOOR FAN MOTOR SHOWING WEAR BY PULLING HIGH AMPS/EXCESSIVELY HEATING AND LEAKING OIL. DUE TO THESE ISSUES WEATHERMASTERS RECOMMENDS REPLACEMENT OF MOTOR AS IT COULD FAIL AT ANY POINT. NO OTHER ISSUES FOUND AT TIME OF INSPECTION FOR RECOMMEND REPAIRS. CUSTOMER WISHES TO MOVE FORWARD WITH REPLACEMENT OF OUTDOOR FAN MOTOR IN MID MAY.

Near E Firestone Dr, Chandler, AZ 85249
Chris R.

Chris R.

PROBLEM NEED TO CALL FOR PRICING DUCT IS 10-3 8" ROUND =8' /4= 8" 90* 8" T-TOP 2' OF 10-3 SQ DUCT WITH CAP PICK UP METAL/10-3 DUCT EVSHEET METAL PICK UP THE REST OF MATERIALS AT WEBB

Near E Libra Pl, Chandler, AZ 85249
Stuart M.

Stuart M.

PERFORMED 37 POINT INSPECTION ON SPLIT GAS AC UNIT CHECKED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURER'S RATING TIGHTENED ELECTRICAL CONNECTIONS CLEANED OFF OUTDOOR COIL VERIFIED TEMP SPLIT ACROSS INDOOR COIL INSPECTED CONDITION OF UNIT UNIT RUNNING NORMALLY IN COOLING AT TIME OF INSPECTION. WEATHER MASTERS RECOMMENDS FOLLOW UP INSPECTION IN FALL FOR HEATING SIDE OF SYSTEM.

Near E Augusta Ave, Chandler, AZ 85249
Stuart M.

Stuart M.

PERFORMED 37 POINT INSPECTION ON TWO SPLIT GAS AC UNITS CHECKED AMP DRAW OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURER'S RATING VERIFIED TEMP SPLITS ACROSS COILS TIGHTENED ELECTRICAL CONNECTIONS INSPECTED CONDITION OF UNITS UPSTAIRS UNIT HAD LOW 45/5 MF DUAL CAPACITOR THAT WAS REPLACED AT TIME OF INSPECTION. BOTH UNITS RUNNING NORMALLY IN COOLING AFTER RECOMMENDED REPAIRS. WEATHER MASTERS RECOMMENDS FOLLOW UP INSPECTION IN FALL FOR HEATING SIDE OF SYSTEM.

Near E Thunderbird Dr, Chandler, AZ 85249
Stuart M.

Stuart M.

PERFORMED 37 POINT INSPECTION ON SPLIT HEAT PUMP UNIT CHECKED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURES RATING CLEANED OFF OUTSIDE COIL TIGHTENED ELECTRICAL CONNECTIONS VERIFIED TEMPERATURE SPLIT ACROSS COIL INSPECTED CONDITION OF UNIT UNIT IS SHOWING RUST CORROSION ON INDOOR COIL DUE TO AGE. SECONDARY DRAIN PAN ALSO SHOWING RUST DAMAGE. UNIT RUNNING IN COOLING AT TIME OF INSPECTION. WEATHER MASTERS RECOMMENDS FOLLOW UP INSPECTION IN FALL FOR HEATING SEASON

Near W Whitten St, Chandler, AZ 85224
Chris R.

Chris R.

START UP ON 2 UNITS ROOM IS 69 DEGREES DURRELL WILL MONITOR AND MAKE SURE THE ROOM HOLDS TEMP AND PUMPS FUNCTION PROPERLY NO CHARGE PER BOYD

Near N 54th St, Chandler, AZ 85226
Stuart M.

Stuart M.

PERFORMED PMP INSPECTION ON GAS FURNACE AND CONVENTIONAL AC TESTED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS FOR PERFORMANCE VERIFIED TEMPERATURE RISE IN HEATING TIGHTENED ELECTRICAL CONNECTIONS TESTED PRESSURE SAFETY SWITCH TEATED FLAME SENSOR SAFETY CHECKED ROLLOUT SAFETY FOR PERFORMANCE VERIFIED TEMPERATURE RISE SAFETY FUNCTIONALITY CHECKED INRUSH AMPS OF COMPRESSOR UNIT RUNNING NORMALLY AT THIS TIME. DUAL RUN CAPACITOR WEAK ON OUT DOOR FAN SIDE BUT WITHIN MANUFACTURER'S SPECIFICATIONS.

Near S Sean Ct, Chandler, AZ 85286
Keith H.

Keith H.

PROBLEM: A/C UNITS WONT TURN OFF. SHUT POWER OFF AT BREAKER. DIAGNOSIS: WHEN I ARRIVED I TURNED THE POWER ON TO BOTH UNITS.. WHEN DOING SO THE ONLY UNIT IT TURN ON WITHOUT THE THERMOSTAT WAS THE NORTH UNIT. I WAS ABLE TO ISOLATE THE ISSUE TO THE MAIN CONTROL BOARD. I SWAPPED THE BOARDS AND THE ISSUE HAPPEND ON THE OPPOSITE UNIT. THE ISSUE IS THE BOARD HAS AN INTERNAL SHORT CAUSING THE SYSTEM TO RUN IN HEATING ENTIRELY. REPAIR: REPLACED THE MAIN CONTROL BOARD IN THE SOUTH UNIT. I WAS ABLE TO LEAVE THE GOOD BOARD IN THE NORTH UNIT. AFTER REPLACING THE BOARDS I WAS ABLE TO FIND THE THERMOSTATS PROGRAMED INCORRECTLY. THIS WAS WEATHER MASTERS DOING YESTERDAY. I WAS ABLE TO REPROGRAM THE AND NOW BOTH SYSTEMS ARE RUNNING JUST FINE IN COOLING AND HEATING..

Near N Delaware Ct, Chandler, AZ 85225
Keith H.

Keith H.

REPLACE RETURN AIR FILTERS. (32) 16X16X2 IN PLEATED FILTERS. WEATHER MASTERS WILL ALSO REPAIR THE 8 CONDENSATE LINES THAT WEATHER MASTERS CUT AND TAPED BACK TOGETHER. WEATHER MASTERS WILL CREDIT THE REPAIR COST OF THE 9TH UNIT DUE TO THEM HAVING A HANDY MAN FIXING THE 1 LINE. CREDIT $250.00

Near W Frye Rd, Chandler, AZ 85224
Stuart M.

Stuart M.

PROBLEM: UNIT BLOWING COLD AIR DIAGNOSIS: UNIT RUNNING IN DEFROST CYCLE DUE TO FREEZING COLD ATMOSPHERIC CONDITIONS. UNIT WAS SHUT OFF BY OWNER AND ICE MELTED NATURALLY DOWN COIL PRIOR TO SERVICE CALL. DURING TIME OF SERVICE CALL UNIT RUNNING NORMALLY IN HEATING

Near E Gleneagle Dr, Chandler, AZ 85249
Chris R.

Chris R.

PROBLEM PMP VISIT 1 UNIT FIRST CO. 18HX5-240 DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT IS HEATING AT THIS TIME AMPS FOR ELECTRIC HEAT STRIPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME /21 AMPS NO RECOMMENDED REPAIRS AT THIS TIME

Near W Ray Rd, Chandler, AZ 85224
Chris R.

Chris R.

PROBLEM PMP VISIT 1 UNIT FIRST CO. 18HX5-240 DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT IS HEATING AT THIS TIME AMPS FOR ELECTRIC HEAT STRIPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME /21 AMPS NO RECOMMENDED REPAIRS AT THIS TIME

Near W Ray Rd, Chandler, AZ 85224
Chris R.

Chris R.

PROBLEM PMP VISIT 1 UNIT FIRST CO. 18HX5-240 DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT IS HEATING AT THIS TIME AMPS FOR ELECTRIC HEAT STRIPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME /21 AMPS NO RECOMMENDED REPAIRS AT THIS TIME

Near W Ray Rd, Chandler, AZ 85224
Chris R.

Chris R.

PROBLEM NO HEAT FIRST CO 36HX0-70 T-STAT SET FOR E-HEAT AFTER SETTING T-STAT FOR HEAT THE HEAT CAME ON HOUSE IS HEATING AT THIS TIME DUE TO RAIN WE WOULD NEED TO RESCHEDULE IF FURTHER DIAGNOSTICS IS NEEDED FOR THE CONDENSER EXPLAINED THE OPERATION OF THE T-STAT TO THE TENANT

Near N Alma School Rd, Chandler, AZ 85224
Chris R.

Chris R.

PROBLEM 37 PT INSPECTION 1 UNIT DAY AND NIGHT N8MPN050B12B2 A101143843 MFD 2010 DIAGNOSIS 10 MFD RUN CAPACITOR FOR THE INDOOR BLOWER MOTOR HAS FAILED /THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTOR VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT IS HEATING WITHIN THE SPECIFIED TEMP RISE ACROSS THE HEAT EXCHANGER MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME TESTED ALL SAFTEY AND LIMIT SWITCHES /NO ISSUES AT THIS TIME REPAIRS REPLACED THE 10 MFD RUN CAPACITOR UNDER WARRANTY

Near S Callaway Dr, Chandler, AZ 85249
Keith H.

Keith H.

WEATHER MASTES PROPOSES TO: - REMOVE AND REPLACE THE OUTDOOR CONDENSER COIL. - REMOVE AND REPLACE LIQUIDE LINE FILTER DRIER. - PRESSURE TEST SYSTEM AND EVACUATE SYSTEM. - RECHARGE THE SYSTEM WITH 10LBS OF NEW R22 FREON. GOODMAN - SERIAL 0910182012 2-4-19 REMOVED AND REPLACED INDOOR EVAP COIL. RECHARGED THE SYSTEM WITH 9.5 LBS OF NEW R22 FREON. - AT THIS TIME THE SYSTEM IS RUNNING IN COOLING WITH A GOOD TEMPATURE SPLIT. NO OTHER REPAIRS NEEDED AT THIS TIME.

Near W Springfield Way, Chandler, AZ 85286
Nicole  P.

Nicole P.

REPLACED ALL AIR FILTERS ON ROOF TOP UNITS

Near W Chandler Blvd, Chandler, AZ 85225
Chris R.

Chris R.

PROBLEM PMP VISIT 1 UNIT CARRIER 58RAV095---16116 1396A13088 DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT IS HEATING WITH A 50 DEGREE TEMPERATURE RISE ACROSS THE HEAT EXCHANGER /THIS IS WITHIN THE SPECIFIED RANGE FOR THIS FURNACE TESTED ALL SAFTEY AND LIMIT SWITCHES /NO ISSUES AT THIS TIME CHECKED MOTOR AMPS AND RUN CAPACITOR /ALL ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME THE UNIT IS SHOWING GENERAL WEAR DUE TO THE AGE AND USAGE NO RECOMMENDED REPAIRS AT THIS TIME

Near W Kesler Ln, Chandler, AZ 85226
Chris R.

Chris R.

PROBLEM PMP VISIT 1 UNIT DAY AND NIGHT FADED DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN HEATING MODE AND THE UNIT HEATING WITH A 53 DEGREE TEMPERATURE RISE ACROSS THE HEAT EXCHANGER /THIS IS WITHIN THE SPECIFIED RANGE FOR THE FURNACE TESTED ALL SAFTEY AND LIMIT SWITCHES /NO ISSUES AT THIS TIME MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME NO RECOMMENDED REPAIRS AT THIS TIME

Near N Bradley Dr, Chandler, AZ 85226
Chris R.

Chris R.

PROBLEM PMP VISIT 2 UNITS TRANE DOWNSTAIRS TUD080C948K4 4034YLD1G MFD:1/2004 UPSTAIRS TUD080C960K4 4403J8F1G MFD:9/2004 DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND AND BOTH UNITS ARE HEATING WITHIN THE SPECIFIED TEMP RISE ACROSS THE HEAT EXCHANGERS TESTED ALL SAFTEY AND LIMIT SWITCHES /NO ISSUES AT THIS TIME 15 AND 10 MFD RUN CAPACITOR FOR THE INDOOR BLOWER MOTORS HAVE FAILED /THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTORS BLOWER MOTORS /WHEELS AND POSSIBLE THE EVAPORATOR COILS ARE DIRTY /DUE TO THE AGE OF THE UNITS WE DON'T RECOMMEND ANY COSTLY REPAIRS /HOME OWNER DECLINED TO PULL AND CLEAN THESE PARTS AT THIS TIME REPAIRS REPLACED 15 AND 10 MFD RUN CAPACITORS FOR THE INDOOR BLOWER MOTORS

Near S Nash Way, Chandler, AZ 85286
Keith H.

Keith H.

PERFORM 37 PT INSPECTION ON SPLIT GAS HEAT STRAIGHT COOL A/C ALSO ADDRESS ISSUES HOME INSPECTOR FOUND. 1- FLU PIPE CLEANCE 2- CONDENSATE ISSUE DUE TO RUSTY FURNACE 3- LEAKING AIR FROM SUPPLY PLENUM 4- INSULATION ON SUCTION LINE. 5- POOR TEMPATURE SPLIT IN COOLING. DIAGNOSIS: ISSUES 1-4 HAVE BEEN ADDRESS AND TAKEN CARE OF. ISSUE 5 IS CAUSED BECAUSE WHILE RUNNING IN COOLING THE OUTDOOR COMPRESSOR AND FREON PRESSURES ARE NOT CORRECT. WEATHER MASTERS PERFORMED AN ELECTRONIC LEAK SEARCH OF THE SYSTEM AND FOUND A FREON LEAK IN THE OUTDOOR CONDENSER COIL. THE OUTDOOR COIL WILL NEED TO BE REPLACED AND THE SYSTEM RECHARGED WITH NEW R22 FREON BEFOR THE UNIT WILL COOL CORRECTLY. TESTED THE FURANCE IN HEATING. VERIFIED SEQUENCE OF OPERATION . THE FURNACE AT THIS TIME IS WORKING FINE WITH NO ISSUES. ALL SAFTY CONTROLS AND TEMPATURE HIGH LIMITS ARE FUNCTIONING CORRECTLY. DUE TO THE ISSUE WITH THE OUTDOOR CONDENSER , WEATHER MASTERS IS UNABLE TO PERFORM A FULL COOLING INSPECTION AT T

Near W Springfield Way, Chandler, AZ 85286
Keith H.

Keith H.

WEATHER MASTERS PURPOSES TO REMOVE AND REPLACE OUTDOOR TXV. WILL RECOVER AND REUSE R-22 REFRIGERANT NOTE: WEATHER MASTERS WILL ADD ADDITIONAL R-22 IF UNIT IS LOW ON CHARGE AT $100.00 PER LB Repair. Replaced valve. System is now heating just fine. Weather masters recommends cleaning the indoor coil and outdoor coil. System needed 2lbs of r22 FREON after recovery.

Near S Galaxy Dr, Chandler, AZ 85226
Chris R.

Chris R.

PROBLEM PMP VISIT 1 UNIT TRANE AUD2C080B9V4VBA 142143PW1G DIAGNOSIS VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT HEATING WITHIN ITS SPECIFIED TEMPERATURE ACROSS THE HEAT EXCHANGER MOTOR AMPS ARE WITHIN MANUFACTURE SPECIFICATIONS 4UF RUN CAPACITOR IS WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME ALL SAFTEY AND LIMIT SWITCHES ARE WORKING AT THIS TIME

Near N Bell Pl, Chandler, AZ 85225
Keith H.

Keith H.

PERFORM HEATING INSPECTION ON 2 SYSTEMS. UPSTAIRS UNIT- UNIT IS HEATING JUST FINE WITH NO ISSUES. TESTED SYSTEM HIGH LIMITS AND SAFTY CONTROLS. UNIT IS HEATING WITH A 30 DEG SPLIT. . DOWNSTAIRS- TESTED SYSTEM IN HEATING AND FOUND IT TO HAVE WATER IN INSIDE THE BLOWER COMPARTMENT. WEATHER MASTES WAS ABLE TO FIND THE WATER IS COMING FROM THE HEAT EXCHANGER COMPARTMENT. THE FURNACE IS A 90% AND DOES PRODUCE CONDENSATE. THE CONDENSATE IS LOCATED INSIDE THE HEAT EXCHANGER.THE SYSTEM HAS A CRACKED HEAT EXCHANGER. THIS IS VERY BAD AND UNSAFE DUE TO THE POSSIBLE CARBON MONOXIDE THAT CAN FILTER INTO THE LIVING SPACE. WEATHER MASTERS DISABLED THE FURNACE FROM BEING ABLE TO HEAT AND ALSO RECOMMENDS REPLACING THE 90 % FURNACE. THE SYSTEM IS 15 YRS OLD AND DUE TO THE AGE AND NATURE OF ISSUE. WEATHER MASTERS RECOMMENDS REPLACING THE ENTIRE SYSTEM.

Near E La Costa Dr, Chandler, AZ 85249