Weather Masters, Inc.  provides plumbing, heating  & Air Conditioning repair and installation services in Mesa, AZ and surrounding areas. Check out what some of our customers are saying about Weather Masters, Inc. Plumbing, Heating & Air Conditioning services.

Local Reviews
for Mesa, AZ

Rated 4.9 out of 5 stars based on 13 customer reviews

Map of Mesa, AZ

HVAC Go To Contractors in AZ




I am a Commercial Property Manager working out of our corporate office in California. When I need HVAC service or a new unit, Weather Masters is who I can trust to do our serivce. They have a competent staff to answer any questions too. I appreciate how they understand the importance of maintaining our systems as long as possible before we make the investment to replace. Great all round company to work with.


Map of Mesa, AZ

Great service!





Map of Mesa, AZ

Great service




Excellent


Map of Mesa, AZ

Thank you for your prompt service.





Map of Mesa, AZ

Great service




Great


Map of Mesa, AZ

Couldn’t be happier!




Everyone has been so professional and kind to work with. Wonderful company that I will highly recommend to everyone I know.


Map of Mesa, AZ

Great Service & Price!




Chris explained everything to me as he went along and let me see the damaged part that caused all the trouble. He really knows his stuff! He also explained the Membership deal and I joined right away. Great discounts have already started!


Map of Mesa, AZ

Great service




Polite, very thorough good experience.


Map of Mesa, AZ

Great service, pleasant technician!





Map of Mesa, AZ

Excellent Job




Very great job. Both technicians could hear the problem, got it diagnosed and fixed. Fantastic job. go one better 6 stars. You guys rocked it. Thank you so much. Now I an get some sleep.


Response from Weather Masters, Inc.:

We appericate your business!! Glad you able to sleep at night!!!


Chris R.

Chris R.

PROBLEM DAMAGED SERVICE DISCONNECT REPAIRS REPLACED 60 AMP FUSED DISCONNECT WARRANTY

Near E Downing St, Mesa, AZ 85207
Chris R.

Chris R.

PROBLEM NO COOL AMANA DIAGNOSIS 45/5 DUAL RUN CAPACITOR HAS FAILED /THIS HAS ALLOWED PERMANENT INTERNAL DAMAGE TO THE COMPRESSOR AND CONDENSER FAN RECOMMEND MAINTENANCE 2 TIMES A YEAR TO HELP WITH THESE ISSUES REPLACED 45/5 DUAL RUN CAPACITOR THE UNIT IS SHOWING HEAVY WEAR DUE TO AGE AND USAGE THE UNIT IS COOLING AT THIS TIME CUSTOMER IS USING 1ST PMP VISIT WE WILL RETURN THURSDAY 3 VISITS LEFT

Near S Greenfield Rd, Mesa, AZ 85206
Chris R.

Chris R.

PROBLEM NO COOL DAY AND NIGHT PHJ448000KTP0A1 C181195561 DIAGNOSIS CAP TUB FOR THE SENSING BULB IS BROKEN OFF REPLACED TXV UNDER LABOR AND PARTS WARRANTY PREFORMED PMP INSPECTION 0/5 DUAL CAP SHOWING WEAR BUT STILL WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME 25 DEGREE TEMP SPLIT ACROSS THE COIL TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COIL FLUSHED DRAIN VERIFIED SEQUENCE OF OPERATION IN THE COOLING MODE AND THE UNIT IS COOLING AT THIS TIME NO CHARGE FOR REPAIRS

Near S Westwood, Mesa, AZ 85210
Stuart M.

Stuart M.

W/O 16241 PROBLEM: UNIT NOT COOLING DIAGNOSIS: UNIT HAS RESTRICTED INDOOR METERING DEVICE. SUPPLY HOUSE DOES NOT LIST SIZE OF ORIFICE THEREFORE WEATHER MASTERS MUST RECOVER EXISTING REFRIGERANT AND REMOVE ORIFICE TO BE EITHER CLEANED OR REPLACED. WEATHER MASTERS CAN NOT GUARANTEE THIS IS THE ONLY ISSUE PRESENT CAUSING RESTRICTION.

Near W Mahoney Ave, Mesa, AZ 85210
Chris R.

Chris R.

PROBLEM NO COOL N4H348AKE100 E110401646 COMPRESSOR IS INTERNALLY DAMAGED IP IS STUCK OPEN BREAKER TRIPPS UPON START UP DIRTY EVAPORATOR COIL DIRTY BLOWER WHEEL AND MOTOR DUE TO AGE AND CONDITION WE RECOMMEND REPLACING THE UNIT

Near E Baseline Rd, Mesa, AZ 85204
Stuart M.

Stuart M.

PERFORMED 37 POINT INSPECTION ON SPLIT HEAT PUMP UNIT CHECKED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS TO BE WITHIN MANUFACTURER'S RATING TIGHTENED ELECTRICAL CONNECTIONS CHECKED STATIC PRESSURE OF AIRFLOW CHECKED REFRIGERANT PRESSURES VERIFIED TEMP SPLIT ACROSS INDOOR COIL INSPECTED CONDITION OF UNIT UNIT HAD LOW 70/5 MF DUAL CAPACITOR TESTING AT 62/4.2MF WHICH IS OUTSIDE THE +/-5% RANGE. CUSTOMER WISHES TO KEEP AN EYE ON THIS CAPACITOR AND REPLACE AT LATER DATE. UNIT RUNNING IN COOLING AT TIME OF INSPECTION.

Near E Natal Ave, Mesa, AZ 85209
Chris R.

Chris R.

PROBLEM NO COOL DAY AND NIGHT T-STAT IMPROPERLY WIRED BLOWN LOW VOLT FUSE IMPROPER VOLTAGE TO THE CONDENSER REWIRED T-STAT REPLACED LOW VOLT FUSE CAN'T VERIFY SEQUENCE OF OPERATION IN THE COOLING MODE UNTIL THEY HAVE POWER AT THE CONDENSER A/H IS WORKING AT THIS TIME OVERALL THIS UNIT IS SHOWING HEAVY WEAR RECOMMEND 37 PT INSPECTION

Near E Baseline Rd, Mesa, AZ 85204
Chris R.

Chris R.

PROBLEM PMP VISIT 2 UNITS /1ST VISIT/3 LEFT DAY AND NIGHT EAST N4H336AKF200 E144508976 VERIFIED SEQUENCE OF OPERATION IN THE COOLING MODE AND THE UNIT IS COOLING AT THIS TIME UNIT IS SHOWING NORMAL WEAR NO RECOMMENDED REPAIRS AT THIS TIME WEST DAY AND NIGHT N4H3366AKF200 E1445509009 THE COMPRESSOR WOULD NOT START I REPLACED THE RUN CAPACITOR AND ADDED A START ASSIST /THE COMPRESSOR DID START BUT THE START ASSIST EXPLODED/CAN'T VERIFY AT THIS TIME IF THE ISSUE WAS THE COMPRESSOR OR JUST A FAULTY START ASSIST INFORMED THE HOME OWNER AND LET THEM KNOW WE NEED TO RUN THE UNIT AND SEE IF THE IISUE HAPPENS AGAIN REPLACED THE 45/5 DUAL RUN CAPACITOR UNDER WARRANTY /DID NOT ADD THE START ASSIST TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COILS FLUSHED DRAINS

Near N Alta Mesa Dr, Mesa, AZ 85205
Chris R.

Chris R.

QUOTE

Near S Salem, Mesa, AZ 85206
Stuart M.

Stuart M.

W/O 16183 PROBLEM: UNIT NOT WORKING IN AC OR HEATING DIAGNOSIS: UNIT HAD BAD RELAY FOR INDOOR BLOWER MOTOR. WEATHER MASTERS REMOVED AND REPLACED RELAY AND BLOWER FIRED UP. UNIT WAS ALSO MISSING PANEL THAT COVERS ELECTRICAL COMPONENTS INSIDE OF UNIT. WEATHER MASTERS FABRICATED NEW PANEL OUT OF SHEET METAL AND SEALED USING TAPE TO PREVENT ANY FURTHER CORROSION DUE TO ELEMENTS.

Near W Ella St, Mesa, AZ 85201
Stuart M.

Stuart M.

PERFORMED 37 POINT INSPECTION ON PACKAGE HEAT PUMP UNIT CHECKED AMP DRAWS OF MOTORS TESTED RUN CAPACITORS FOR PERFORMANCE CHECKED TEMPERATURE SPLIT CHECKED REFRIGERANT PRESSURES TIGHTENED ELECTRICAL CONNECTIONS INSPECTED CONDITION OF UNIT UNIT SHOWING HEAVY RUST DAMAGE ON INDOOR COIL. UNIT ALSO HAS WEAK 12.5 AND 80 MF RUN CAPACITORS. WEATHER MASTERS RECOMMENDS REPLACING BOTH WEAK CAPACITORS TO PREVENT ANY UNNECESSARY DAMAGE TO MOTORS. WEATHER MASTERS ALSO RECOMMENDS REGULAR INSPECTIONS BE PERFORMED ON THE UNIT DUE TO AGE AND WEAR

Near E Huber St, Mesa, AZ 85201
Chris R.

Chris R.

REMOVE AND HAUL AWAY EXISTING 3 TON CK H/P AND ALL DEBRIS INSTALL NEW 14 SEER DAY & NIGHT PACKAGE HEAT PUMP NEW SHEET METAL ELBOW AND ANGLE IRON STAND CONNECT TO EXISTING ROOF JACK USE EXISTING DUCTS BELOW ROOF CONNECT TO EXISTING DRAINS/OFF ROOF CONNECT TO EXISTING ELECTRICAL NEW HONEYWELL 5000 NON PROGRAMMABLE T-STAT NEW 24-16 BAR STYLE FILTER GRILL NEW DISCONNECT AND WHIP/FUSES PROVIDE CRANE SERVICE WEATHER MASTERS CAN NOT BE RESPONSIBLE FOR ANY DRYWALL/PAINT REPAIRS WARRANTY 1YR LABOR 10YR PARTS AND COMPRESSOR

Near W Laguna Azul Ave, Mesa, AZ 85210
Chris R.

Chris R.

PROBLEM 37 PT INSPECTION @2 LENNOX UPSTAIRS 14HPX-048-230-19 1916C50588 70/10 MFD RUN CAPACITOR IS WEAK /THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTORS /RECOMMEND REPLACING EVAPORATOR COIL IS A LITTLE DIRTY/THIS WILL EFFECT THE EFFICIENCY OF THE UNIT AND CAUSE INTERNAL DAMAGE TO THE COMPRESSOR /RECOMMEND CHEMICALLY CLEANING THE COIL IN PLACE THE REFRIGERANT CHARGE LOOKS OK AT THIS TIME THE UNIT HAS A 20 PLUS DEGREE SPLIT ACROSS THE EVAPORATOR COIL DOWNSTAIRS LENNOX 14HPX-048-230-19 1916C50576 70/10 MFD RUN CAPACITOR IS WEAK /THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTORS /RECOMMEND REPLACING EVAPORATOR COIL IS A LITTLE DIRTY/THIS WILL EFFECT THE EFFICIENCY OF THE UNIT AND CAUSE INTERNAL DAMAGE TO THE COMPRESSOR /RECOMMEND CHEMICALLY CLEANING THE COIL IN PLACE THE REFRIGERANT CHARGE LOOKS OK AT THIS TIME THE UNIT HAS A 20 PLUS DEGREE SPLIT ACROSS THE EVAPORATOR COIL TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COILS FLUSHED DRAINS

Near N Paseo Del Sol, Mesa, AZ 85207
Nicole  P.

Nicole P.

WEATHER MASTERS COMPLETED THE FOLLOWING: - REMOVE AND HAUL AWAY EXISTING 7.5 TON LENNOX ROOFTOP PACKAGE HEAT PUMP. - WEATHER MASTERS WILL INSTALL NEW ROOFTOP CURB ADAPTOR. - WEATHER MASTERS WILL INSTALL NEW 7.5 TON DAY AND NIGHT PACKAGE HEAT PUMP. W/ OUT DOOR FRESH AIR. - WEATHER MASTERS WILL INSTALL NEW 60 AMD FUSED SERVICE DISCONNECT WITH NEW FUSES. - WEATHER MASTERS WILL INSTALL NEW HONEYWELL 8000 PROGRAMABLE THERMOSTAT. - WEATHER MASTERS WILL INSTALL NEW SMOKE DETECTOR WITH ALARM SWITCH - WEATHER MASTERS WILL INSTALL NEW SMOKE DETECTOR OUTDOOR COVER. WARRANTY- 1 YR PARTS 5 YR COMPRESSOR. 1 YR LABOR PRICE INCLUDES LABOR, MATERIAL , CRANE TO COMPLETE THE JOB QUOTE VALID FOR 30 DAYS.

Near S Dobson Rd, Mesa, AZ 85202
Keith H.

Keith H.

They have spent 6 months looking for a water leak at the Thai House. Joel wants us to go out and do whatever it takes to find the leak. If it is under the unit on the roof, h would like us to come out next week and remove the unit so he can have the roofers fix the issue. KEITH- Please call Joel when you know what is going on. 602-690-8260 LARRY DISPATCHED TO THE THI HOUSE. ONCE ARRIVED, THE EMPLOYEES DIRECTED LARRY TO THE LEAK. THE LEAK IS IN THE KITCHEN ABOVE THE DISHWASHING STATION. THE TILES BELOW THE LEAK WERE DISCOLORED FROM WATER. A VISUAL INSPECTION WAS DONE IN THE CEILING. THERE IT WAS SEEN THAT THERE IS A LEAK COMING FROM THE COOLER ON THE EAST SIDE WHERE THE DUCT WORK CONNECTS TO THE COOLER ON THE ROOF. PICTURES WERE TAKEN TO HELP DIAGNOSE. A VISUAL INSPECTION WAS THEN DONE ON THE ROOF. THE COOLER IS SEALED WITH TAR BUT THERE IS A LEAK SOMEWHERE ON THE EAST SIDE.

Near S Power Rd, Mesa, AZ 85206
Chris R.

Chris R.

Replace Coil/TXV and Run Cap REPAIRS REPLACED EVAPORATOR COIL AND TXV/NORTH UNIT REPLACED 45/5 DUAL RUN CAPACITOR /NORTH UNIT REPLACED 45/5 DUAL RUN CAPACITOR /SOUTH UNIT ALL PARTS UNDER WARRANTY BOTH UNITS ARE COLLING AT THIS TIME HOSED OFF OUTDOOR COILS TIGHTENED ALL ELECTRICAL CONNECTIONS FLUSHED DRAINS

Near N Alta Mesa Dr, Mesa, AZ 85205
Keith H.

Keith H.

37 PT SRP COOLING INSPECTION. DIAGNOSIS: TESTED SYSTEM IN HEATING AND COOLING. WHEN INSPECTING THE AIR HANDLER . WEATHER MASTERS NOTICED MOLD IN THE BLOWER AND COIL SECTION. THIS IS CAUSED MOST COMMON FROM POOR AIR FLOW. WEATHER MASTERS CHECKED STATIC AIR FLOW AND FOUND THE SYSTEM TO BE RUNNING LOW. ABOUR 1200 CFM. 400 LESS. WEATHER MASTERS INSPECTED RETURN FILTER AND AIR REGISTERS. FOUND THE REGISTERS TO BE CLOSED AND THE SYSTEM TO HAVE A VERY DIRTY FILTER. WEATHER MASTERS OPENED THE REGISTERS REMOVED THE DIRTY AIR FILTER AND ADJUSTED FAN SPEED . THE SYSTEM IS NOW MOVING 1600 CFM . NORMAL FOR A 4 TON SYSTEM. WEATHER MASTERS ALSO FOUND THE PRIMARY DRAIN PAN IS CRACKED . THE PAN WILL NEED TO BE REPLACED. WEATHER MASTES FOUND THE CRACK BY TESTED THE DRAIN WITH FRESH WATER. WEATHER MASTERS RECOMMEDS A COIL CLEANING AT TIME OF PAN REPLACMENT. WEATHER MASTERS TESTED THE OUTDOOR CONDENSER AND FOUND THE UNIT TO HAVE A WEAK 70-7.5 DUAL RUN CAPACITOR. WEATHER MASTERS REPLACI

Near E Ivy St, Mesa, AZ 85205
Chris R.

Chris R.

PROBLEM 37 PT INSPECTION 1 UNIT ICP PHD342000K000C1 C133027654 DIAGNOSIS CONDENSER FAN MOTOR HAS BEARING DAMAGE /MOTOR MAY FAIL PREMATURELY /THIS WILL CAUSE INTERNAL DAMAGE TO THE COMPRESSOR /RECOMMEND REPLACING SOON 45/5 DUAL RUN CAPACITOR IS SHOWING WEAR BUT STILL WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME OVERALL THE UNIT IS SHOWING NORMAL WEAR DUE TO AGE AND USAGE TIGHTENED ALL ELECTRICAL CONNECTIONS HOSED OFF OUTDOOR COIL FLUSHED DRAIN VERIFIED SEQUENCE OF OPERATION IN THE COOLING MODE AND THE UNIT IS COOLING AT THIS TIME

Near Leisure World, Mesa, AZ 85206
Chris R.

Chris R.

PROBLEM LEAK DIAGNOSIS DRAIN IMPROPERLY PIPED 115 V PUMP FAILED REPAIRS FIX DRAIN FITTING REPLACED 115 V PUMP OILED BEARINGS AND MOTOR

Near E Main St, Mesa, AZ 85213
Chris R.

Chris R.

PROBLEM PMP VISIT @2 SOUTH UNIT DAY AND NIGHT N4H336AKF200 E144509003 AH FXM4X3600AL3 NORTH UNIT N4H336AKF200 E144521036 DIAGNOSIS SOUTH UNIT IS LOW ON CHARGE/PREFORMED LEAK SEARCH AND FOUND A LEAK AT THE EVAPORATOR COIL /COMPRESSOR MAY HAVE TAKEN INTERNAL DAMAGE IF IT RAN WILL LOW ON REFRIGERANT CAN'T FINISH THE INSPECTION AT THIS TIME NORTH UNIT HAS A WEAK 45/5 DUAL RUN CAPACITOR /THIS WILL ALLOW INTERNAL DAMAGE TO THE MOTORS/RECOMMEND REPLACING CAP REFRIGERANT CHARGE IS WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME AMPS FOR ALL MOTORS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME TIGHTENED ALL ELECTRICAL FLUSHED DRAINS HOSED OFF OUTDOOR COILS NORTH UNIT IS COOLING AT THIS TIME SOUTH UNIT IS NOT COOLING AT THIS TIME $1287 RETURN 3/11

Near N Alta Mesa Dr, Mesa, AZ 85205
Keith H.

Keith H.

SRP 37 PT INSPECTION. DIAGNOSIS: TESTED SYSTEM IN COOLING. FOUND THE UNIT TO BE RUNNING NORMAL. UNIT IS SHOWING NORMAL WEAR DUE TO AGE. THE CONDENSER FAN MOTOR IS RUNNING WARM BUT STILL WORKING FINE. THE INDOOR AIR HANDLER LOOKS NORMAL HOWEVER THE CONDENSATE LINE IS IMPROPERLY PIPED . THIS MAY CAUSE ISSUES WITH THE CONDENSATE LINE DRAINING CORRECTLY. WEATHER MASTES HOSED OFF THE OUTDOOR COIL. FLUSHED THE CONDENSATE LINE. TIGHTEN ELECTRICAL CONNECTIONS. CHECKED FREON LEVELS. VERIFIED MOTOR AMP DRAWS AND RUN CAPACITORS. RECOMMEND: REPLACING OUTDOOR FAN MOTOR DUE TO THE HIGH RUNNING TEMPATURE AND ADDING A P-TRAP TO THE CONDENSATE LINE. RECOMMEND WEATHER MASTERS PMP MAINTENANCE PROGRAM FOR FUTURE SAVINGS ON REPAIRS AND INSPECTIONS.

Near E Des Moines St, Mesa, AZ 85207
Keith H.

Keith H.

PROBLEM: INSTALL NEW HONEYWELL 8000 WIFI THERMOSTAT. WEATHER MASTES WAS ABLE TO INSTALL A NEW HONEYWELL 8000 THERMOSTAT FOR THE DOWNSTAIRS A/C . WEATHER MASTERS DID VERIFY OPPERATION OF NEW STAT. I SPOKE WITH JOSH ABOUT REGISTERING THE DEVICE WITH HIS HONEYWELL ACCOUNT. HE IS AWARE OF HOW TO DO THIS AND WILL TAKE CARE OF IT WHEN HE GETS HOME.

Near E Spaulding Ave, Mesa, AZ 85212
Chris R.

Chris R.

PROBLEM NO COOL LENNOX CHP20R-461-2P 5600A00963 BURNED /DAMAGED COMPRESSOR CONTACTOR BURNED WIRES AT COMPRESSOR IMPROPERLY FUSES/NEED 50 AMP FUSES BAD BREAKER IN MAIN PANEL /NEED ELECTRICIAN TO REPLACE BREAKER CAN'T VERIFY ISSUE UNTIL BREAKER IS REPLACED REPLACED CONTACTOR

Near W Edgewood Ave, Mesa, AZ 85210
Chris R.

Chris R.

37 PT INSPECTION PULL AND CLEAN BLOWER WHEEL CHEMICALLY CLEAN EVAPORATOR COIL IN PLACE REPAIRS CHEMICALLY CLEANED EVAPORATOR COIL AND BLOWER WHEEL

Near N Mesa Dr, Mesa, AZ 85201
Keith H.

Keith H.

SRP $69.95 INSPECTION. DIAGNOSIS: TESTED THE SYSTEM IN BOTH HEATING AND COOLING AND FOUND THE SYSTEM TO BE RUNNING NORMALLY. I DID FIND THE COMPRESSOR RUN CAPACITOR 30MFD IS WEAK AND I WOULD RECOMMEND REPLACING. DURING THE INSPECTION I FOUND THE ELBOW TO BE LEAKING RETURN AIR AND THIS CAN CAUSE DIRT TO GET INTO THE COIL. I WOULD RECOMMEND HAVING IT SEALED. INSPECTION INCLUDE TESTED FREON LEVELS. MOTOR AMP DRAWS AND TIGHTENING ELECTRICAL CONNECTION. SYSTEM AT THIS TIME IS RUNNING NORMAL BUT ONLY HAS A COUPLE ISSUES I WOULD RECOMMEND REPAIRING.