PROBLEM FILTER MAINTENANCE REPLACED 10@20-20

Near W Geneva Dr, Tempe, AZ 85282
Stuart M.

Stuart M.

PERFORMED 37 POINT INSPECTION ON PACKAGE HEAT PUMP UNIT TESTED AMP DRAW OF MOTORS CHECKED RUN CAPACITORS FOR PERFORMANCE WITHIN MANUFACTURER'S RATING VERIFIED TEMPERATURE SPLIT ACROSS COIL TIGHTENED ELECTRICAL CONNECTIONS INSPECTED CONDITION OF UNIT UNIT HAD LOW 5MF RUN CAPACITOR FOR OUTDOOR FAN MOTOR TESTING AT 3.7MF CAUSING EXTRA WEAR TO THE MOTOR. CAPACITOR WAS REPLACED AT TIME OF INSPECTION AND UNIT RUNNING NORMALLY IN COOLING.

Near S Country Club Way, Tempe, AZ 85282
Stuart M.

Stuart M.

INSPECTED INSIDE FOR A LEAK. MOISTURE WAS FOUND RUNNING BETWEEN THE DUCT AND INSULATION ON THE UNDERSIDE. AFTER FURTHER INSPECTION ON THE OUTDOOR UNIT, A POSSIBLE LEAK WAS FOUND IN THE SEALANT CONNECTIONG THE TRANSITION DUCT WORK TO THE ROOF, UNDERNEATH THE AC DUCTWORK. INFORMED THE CUSTOMER THAT THEY WOULD NEED TO CONTACT A ROOFER TO SEAL THE ROOF TO STOP THE LEAK.

Near S Rural Rd, Tempe, AZ 85283
Keith H.

Keith H.

UNIT 8- TEDDY LOUNGE, DEFROST CONTROL BOARD THATS NOT WORKING. Unit 21- / defrost board and sensor bad

Near S Rural Rd, Tempe, AZ 85283
Keith H.

Keith H.

PMP INSPECTION. 2 UNITS. DIAGNOSIS: CHECKED AMP DRAWS ON OUTDOOR AND INDOOR UNITS. CLEANED OUTDOOR COILS WITH WATER. CHECKED PRESSURES AND REFRIGERANT LEVELS ON BOTH UNITS. REFRIGERANT LEVELS ARE OK. LEAK CHECKED CONDENSATE LINES AND PANS. TIGHTENED ELECTRICAL CONNECTIONS. VERIFIED SEQUENCE OF OPERATIONS IN BOTH HEATING AND COOLING. BOTH SYSTEMS SHOWING NORMAL WEAR FOR AGE. RECOMMEND: NEXT SERVICE IN THE FALL.

Near S Grandview Dr, Tempe, AZ 85284
Chris R.

Chris R.

PROBLEM NO COOL #15981 TRANE YCY042G1M0AD 5424LWL1H MFD:10/2005 DIAGNOSIS INDOOR BLOWER MOTOR HAS FAILED /THIS HAS ALLOWED PERMANENT INTERNAL DAMAGE TO THE COMPRESSOR EVAPORATOR COIL IS RUSTED AND DIRTY INDOOR BLOWER MOTOR IS DIRTY DRAIN PAN IS FULL OF DIRT AND DEBRIS THIS UNIT HAS A VARIABLE SPEED BLOWER MOTOR /RUNNING THIS MOTOR WITH A DIRTY COIL AND OR DIRTY BLOWER WHEEL WILL CAUSE INTERNAL DAMAGE TO THE MOTOR WE RECOMMEND CLEANING THE COIL,BLOWER WHEEL AND DRAIN PAN ALONG WITH THE MOTOR REPLACEMENT **DUE TO THE AGE AND CONDITION OF THIS UNIT WEATHER MASTERS RECOMMENDS REPLACING THE SYSTEM

Near S Terrace Rd, Tempe, AZ 85282
Stuart M.

Stuart M.

PROBLEM: UNIT NOT HEATING DIAGNOSIS: UNIT HAS A BAD THERMOSTAT ATTACHED TO SYSTEM. WEATHER MASTERS WAS ABLE TO FIRE UP THE UNIT BY BYPASSING THERMOSTAT INDICATING NO OTHER ISSUES WERE PRESENT. MANAGEMENT AT THE APARTMENT WAS INFORMED OF THE DIAGNOSIS AND WISHES TO HAVE IN HOUSE TECHNICIANS REMOVE AND REPLACE THERMOSTAT.

Near S Priest Dr, Tempe, AZ 85282
Chris R.

Chris R.

PROBLEM NOISE #15666 DIAGNOSIS FILTER IS CAUSING THE NOISE/RECOMMEND LESS RESTRICTIVE FILTER

Near S Granada Dr, Tempe, AZ 85282
Chris R.

Chris R.

PROBLEM NOISE #15666 DIAGNOSIS FILTER IS CAUSING THE NOISE/RECOMMEND LESS RESTRICTIVE FILTER

Near S Granada Dr, Tempe, AZ 85282
Chris R.

Chris R.

PROBLEM NOISE #15666 DIAGNOSIS FILTER IS CAUSING THE NOISE/RECOMMEND LESS RESTRICTIVE FILTER

Near S Granada Dr, Tempe, AZ 85282
Keith H.

Keith H.

WEATHER MASTERS WILL REMOVE AND REPLACE WARRANTY COMPRESSOR. WEATHER MASTERS WILL INSTALL NEW BI FLOW FILTER DRIER, RUN CAPACITOR AND START CAPACITOR, WEATHER MASTERS WILL USE 9 LBS OF NEW F410A FREON .

Near S Farmer Ave, Tempe, AZ 85283
Keith H.

Keith H.

PROBLEM: FREEE SECOND OPINION. DIAGNOSIS: 3 TON PACKAGE HEAT PUMP SYSTEM NOT HEATING OR COOLING. THE COMPRESSOR HAS A FAILED CAPACITOR. BURNED UP START DISC AND A LOCKED UP COMPRESSOR. THE COMPRESSOR WILL NEED TO BE REPLACED IN ORDER TO RESTORE FUCTION TO THE SYTEM. WEATHER MASTERS WILL PROVIDE ESTIMATE FOR REPAIRS. NORDYNE MODEL - Q7RD-036K SERIAL Q7F141060077

Near S Farmer Ave, Tempe, AZ 85283
Chris R.

Chris R.

CHECKED UNIT UNIT IS SHOWING WEAR DUE TO AGE AND USAGE 45/5 DUAL RUN CAPACITOR IS OK AT THIS TIME AMPS FOR ALL MOTORS ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME TESTED DEFROST CYCLE /NO ISSUES AT THIS TIME CONDENSER FAN MOTOR IS SHOWING WEATHER WEAR THE UNIT IS HEATING WITH A 25 DEGREE TEMP SPLIT ACROSS THE EVAPORATOR COIL CHECKED THE SEAL ON THE DUCT AT THE UNIT /NO ISSUES ANY OTHER ISSUES WE RECOMMEND A ROOFER

Near E Loma Vista Dr, Tempe, AZ 85282
Stuart M.

Stuart M.

Perform heating inspections on HVAC equipment. Unit 1 - Low/Weak 5MFD Outdoor fan motor UNIT 8- TEDDY LOUNGE, UNIT HAS A WEAK 3MFD CAPACITOR AND A DEFROST CONTROL BOARD THATS NOT WORKING. Unit 9- weak 10 cap UNIT 10- UNIT HAS A ODF MOTOR THAT IS OVER AMPING . RECOMMEND REPLACEMENT. UNIT 18- WEAK 5MFD CAPACITOR , ODF MOTOR OVER AMPING. RECOMMEND REPLACEMENT. Unit 21- weak 45-5 cap / defrost board and sensor bad UNIT 23 - ODF MOTOR LEAKING OIL AND OVER AMPING. RECOMMEND REPLACING MOTOR Class 4- 55-5 weak / split system Unit 11 and 12 weak 10-10 dual caps

Near S Rural Rd, Tempe, AZ 85283
Chris R.

Chris R.

#15623 /NOISE S/A REGISTER ADJUSTABLE DAMPER IS VIBRATING/RECOMMEND REPLACING 12/6 SIDEWALL TENANT NOT HOME TO VERIFY ISSUE/NEIGHBOR GAVE ME ACCESS REPAIRS ADJUSTED DAMPER AND NOISE STOPPED FOR NOW WILL PROVIDE ESTIMATE APPON REQUEST

Near S Granada Dr, Tempe, AZ 85282
Chris R.

Chris R.

NEED TO RESCHEDULE - Chris arrived and customer was mistaken that we were only coming out to look at the Pigeon issue and not perform the PMP yet. PMP VISIT 1 UNIT GOODMAN PHKJ048-1C 0408089629 DIAGNOSIS UNIT IS SHOWING HEAVY WEAR DUE TO AGE AND USAGE VERIFIED SEQUENCE OF OPERATION IN THE HEATING MODE AND THE UNIT IS HEATING WITH A 25 DEGREE TEMP SPLIT ACROSS EVAPORATOR COIL TESTED DEFROST CYCLE /NO ISSUES AT THIS TIME TESTED 60/5 DUAL RUN CAPACITOR /SHOWING WEAR BUT STILL WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME CHECKED ALL MOTOR AMPS /ALL ARE WITHIN MANUFACTURE SPECIFICATIONS AT THIS TIME NO RECOMMENDED REPAIRS AT THIS TIME

Near E Don Carlos, Tempe, AZ 85281
Chris R.

Chris R.

Perform heating inspections on HVAC equipment. WEATHER MASTERS TIGHTEN ELECTRICAL CONNECTIONS, TESTED FREON LEVELS AND MOTOR AMP DRAWS, WEATHER MASTERS INSPECTED INDOOR AND OUTDOOR COILS. WEATHER MASTERS TESTED HEATING DEFROST CYCLE SEQUENCE OF OPPERATION. ALL OF THE UNITS ARE RUNNING IN HEATING AND SOME UNITS HAVE ISSUES. LIST OF RECOMMENDED REPAIRS ARE TO LIMIT HEATING AND COOLING FAILURES IN THE FUTURE. RECOMMENED REPAIRS- Unit 1 - low weak 5mfd for outdoor fan motor Unit2- system is very old. Compressor is noisy. Recommend unit replacement Unit 3- unit compressor is noisy unit is very old. Recommend unit replacement UNIT 8- TEDDY LOUNGE, UNIT HAS A WEAK 3MFD CAPACITOR AND A DEFROST CONTROL BOARD THATS NOT WORKING. Unit 9- weak 10 cap UNIT 10- UNIT HAS A ODF MOTOR THAT IS OVER AMPING . RECOMMEND REPLACEMENT. UNIT 18- WEAK 5MFD CAPACITOR , ODF MOTOR OVER AMPING. RECOMMEND REPLACEMENT. Unit 21- weak 45-5 cap / defrost board and sensor bad UNIT 23 - ODF MOTOR LEAKING O

Near S Rural Rd, Tempe, AZ 85283
Chris R.

Chris R.

NEED TO RESCHEDULE

Near E Don Carlos, Tempe, AZ 85281
Keith H.

Keith H.

PROBLEM: EAST MPR ROOM RUNNING IN COOLING. DIAGNOSIS: THE SYSTEM WAS RUNNING IN COOLING , HOWEVER THE THERMOSTAT WAS SET IN HEAT. THE THERMOSTAT WAS SENDING THE WRONG SINGLE OUT. RECOMMEND REPLACING THE THERMOSTAT REPAIR: WEATHER MASTERS INSTALLED A NEW HONEYWELL 8000 REDLINK 2STAGE COOLING THERMOSTAT. THE SYSTEM IS NOW RUNNING IN HEATING JUST FINE WITH NO ISSUES.

Near S Rural Rd, Tempe, AZ 85283
Keith H.

Keith H.

wo15092 PROBLEM: INDOOR FAN NOT RUNNING IN HEATING.. ONLY IN A/C DIAGNOSIS: THE INDOOR FAN DOESNT START RUNNING UNTILL THE PRESSURES OF THE UNIT BUILD UP TO HEAT. IN AC THE FAN WILL TURN ON RIGHT AWAY BUT WILL NOT IN HEATING. AT THIS TIME THE UNIT WILL WORK IN HEATING JUST FINE. THE TENANT NEEDS TO LEAVE THE AIR HANDLER ON LONG ENOUGH TO ALLOW THE FAN TO TURN ON. FOR SOME MINI SPLITS THIS IS NORMAL.

Near S Hardy Dr, Tempe, AZ 85281
Chris R.

Chris R.

PROBLEM: ROOM 201 NOT KICKING ON. DIAGNOSIS: WHEN I ARRIVED THE ROOM WAS BEING USED AND COULDNT GET ACCESS. THE PERSON OPEN THE DOOR AND SAID THE UNIT WAS HEATING. I TALKED TO STEVE AND HE SAID TO CANCEL THE WORK ORDER. WEATHER MASTERS WILL STILL CHARGE A SERVICE CALL FEE FOR TRAVEL. DIAGNOSIS RM 201 FIRST CO. 513B024005BFC BTB718A100A1 232064U20 THE UNIT SHOWS A RESTRICTION AT THE EVAPORATOR POSSIBLE LOW CHARGE COMPRESSOR IS DAMAGED THE GUEST HAVE BEEN RUNNING THE UNIT IN LOW AMBIENT CONDITIONS DUE TO AGE AND CONDITION WE RECOMMEND REPLACING THE SYSTEM

Near S 48th St, Tempe, AZ 85281
Keith H.

Keith H.

PROBLEM: ROOM 201 NOT KICKING ON. DIAGNOSIS: WHEN I ARRIVED THE ROOM WAS BEING USED AND COULDNT GET ACCESS. THE PERSON OPEN THE DOOR AND SAID THE UNIT WAS HEATING. I TALKED TO STEVE AND HE SAID TO CANCEL THE WORK ORDER. WEATHER MASTERS WILL STILL CHARGE A SERVICE CALL FEE FOR TRAVEL.

Near S 48th St, Tempe, AZ 85281
Keith H.

Keith H.

PROBLEM: UNIT IS COOLILNG AND HEATING FINE. HOWEVER THE OUTDOOR UNIT EARLY IN THE MORNING MAKES A LOUD SWOOSH NOISE WHEN THEN SYSTEM TURNS OFF. DIAGNOSIS: WEATHER MASTES WAS ABLE TO REPLICATETEH NOISE WITH DEFROST CYCLE. THE HOMEOWNER SAID THIS IS WHAT HE HEARS. WEATHER MASTERS EXPLAINED HOW THE DEFROST CYCLE WORKS AND THE HOMEOWNER IS NOW AWARE. THE UNIT FREON PRESSURES AND TEMPATURES CHECK FINE AT TH IS TIME. NO ISSUES WITH THE EQUIPMENT RIGHT NOW.

Near E Stephens Dr, Tempe, AZ 85283
Chris R.

Chris R.

PROBLEM NO HEAT TRANE TUD080C948K2 3173PRD2G DIAGNOSIS VACUUM PRESSURE SWITCH IS TRIPPING DUE TO A FLUE PIPE RESTRICTION REPAIRS ADJUSTED FLUE PIPE CAP PRESSURE SWITCH MAY HAVE TAKEN INTERNAL DAMAGE BUT FURNACE IS OPERATING AT THIS TIME

Near S Priest Dr, Tempe, AZ 85282
Keith H.

Keith H.

Wo14966 REPAIR FREON LEAK LOCATED AT MECHANICAL FLAIR CONNECTION FOR INDOOR TXV VALVE,. THE MECHANICAL CONNECTIONS NEEDS TO BE REPAIRED. INCLUDES- -REPAIRING FLAIR CONNECTION BY REPLACING WITH A BRAZED CONNECTION. -REPLACING BIFLOW FILTER DRIER -PRESSURE TESTING THE SYSTEM -RECHARGEING THE UNIT WITH THE FACTORY RECOMMENDED FREON CHARGE OF 9.5LBS OF R410A.

Near E 5th St, Tempe, AZ 85281